The position of the dipswitch corresponds to the address, the following ta-
ble shows 16 possible combinations.
Dipswitch No.
Address
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
1 off off off off off off off off ON ON ON ON ON ON ON ON
2 off off off off ON ON ON ON off off off off ON ON ON ON
3 off off ON ON off off ON ON off off ON ON off off ON ON
4 off ON off ON off ON off ON off ON off ON off ON off ON
+
- No specific order is required when assigning addresses, although, de-
vices of the same type must have different addresses. Keypads and key
readers can have the same address as they are intrinsically different.
- On initial Startup the Control panel will assign address 1 to the Keypad
(refer to BPI configuration).
-Dipswitch no.1 of the keypads must always be OFF.
BPI bus length
Due to voltage drops and stray capacitance caused by the Main Unit BPI
bus connections, the BPI bus must not exceed the recommended length.
A voltage of 10 V or over, across Main Unit terminals [+] and [--] is required
for proper functioning of the BPI devices. When 10 V is not available try:
Ø Increasing the wire section that supplies the voltage to the device (wires
connecting terminals [+] and [--] of the Main Unit to terminals [+] and [--] of
the devices).
Ø Generating power by means of a Power Station (BXM12).
+
500 m is the maximum cable length for the connection of any BPI device to
the Main Unit. The overall cable length (connected to the BPI bus of the
Main Unit) must not exceed 1,000 m.
22 Security System Control Panels Omnia8/Omnia4