Balanced 10K The zone will be in Standby status when it is connected to negative
through a 10 K (10,000 ohm) resistor. The Control Panel will generate a
tamper event if the zone switches to ground (negative). The Control Panel
will generate a zone alarm if the zone is unbalanced (zone open).
Double Balanced The zone will be in Standby status when it is connected to negative
through two 10 K (10,000 ohm) resistors. The Control Panel will generate
a zone alarm if one of the resistors disconnects. The Control Panel will
generate a tamper event in all other cases (open zone, zone connected to
negative, etc.).
Alarm cycles
Select the number of cycles for the alarm relay (0 through 14 cycles). Each
zone can be programmed separately.
No cycle The zone will not generate any alarm cycles.
Non-repetitive The zone will signal violation (alarm) for the programmed number of times.
Further violation of the zone will not generate any kind of alarm until the:
Ø Control panel is rearmed.
Ø Alarm memory of one or more of its partitions is reset.
Ø Stop-alarm status ceases on one or more of its partitions (via keypad by
means of a Code PIN or via key reader by means of digital key).
Ø Programming session ends (via keypad or by means of local or remote
connection).
Repetitive The zone will generate an unlimited number of alarm cycles.
+
Zones with a persistent alarm condition (e.g. due to trouble) will generate
one alarm cycle only, as per CEI 79/2 requirements.
Partitions
Alarm zones Assign the zone to one or more of the 4 partitions in the partition section
(select the required partition). The partition codes, digital keys, and pro-
grammed times will be enabled on the zone. A violated zone with more
than one partition will generate alarm when all its partitions are armed. A
violated zone that can generate 24h alarms (24h zone, Duress, Fire or
Zone Tamper for balanced or double balanced zones) will generate alarm
whether the partitions it is assigned to are armed or disarmed. Delayed
zones with more than one partition, will have the Entry or Exit times of the
partition with the highest values.
Command zones Select the partitions for the programmed command.
PROGRAMMING 43